EXXON CO USA, A DIV OF EXXON CORP. -- JET FUEL GRADE JP-5 -- 9140-01-154-5136
=====================  Product Identification  =====================

Product ID:JET FUEL GRADE JP-5
MSDS Date:08/31/1989
FSC:9140
NIIN:01-154-5136
MSDS Number: BJPVS
=== Responsible Party ===
Company Name:EXXON CO USA, A DIV OF EXXON CORP.
Address:800 BELL ST
Box:2180
City:HOUSTON
State:TX
ZIP:77252-2180
Country:US
Info Phone Num:713-656-5949
Emergency Phone Num:713-870-6000/713-656-2443
CAGE:29700
=== Contractor Identification ===
Company Name:EXXON COMPANY U.S.A.
Box:2180
City:HOUSTON
State:TX
ZIP:77252-2180
Country:US
Phone:713-656-5949 / 713-656-3424
CAGE:29700

=============  Composition/Information on Ingredients  =============

Ingred Name:HYDROTREATED LIGHT PETROLEUM DISTILLATE
CAS:64742-47-8
Fraction by Wt: 100%
Other REC Limits:NONE SPECIFIED
OSHA PEL:100 PPM
ACGIH TLV:100 PPM

Ingred Name:ANTIOXIDANT AND METAL DEACTIVATOR
Fraction by Wt: <0.01%
Other REC Limits:NONE SPECIFIED

=====================  Hazards Identification  =====================

LD50 LC50 Mixture:LD50 (ORAL RAT) IS ESTIMATED > 5 G/KG
Routes of Entry: Inhalation:YES  Skin:YES  Ingestion:YES
Reports of Carcinogenicity:NTP:NO    IARC:NO	OSHA:NO
Health Hazards Acute and Chronic:EYE:IRRITATION. SKIN:MILDLY
    IRRITATING. PROLONGED CONTACT MAY CAUSE DERMATITIS AND TISSUE
    DEFATTING. INHALATION:RESPIRATORY SYSTEM IRRITATION AND LIGHT
    HEADEDNESS. MAY CAUSE NAUSEA, HEADACHE, DROWSINE SS, VOMITING.
    INGESTION:SOLVENT ASPIRATION INTO LUNGS AS A RESULT OF VOMITING MAY
    CAUSE LUNG AND DIGESTIVE SYSTEM DAMAGE
Explanation of Carcinogenicity:NONE OF THE MATERIALS LISTED BY THE
    MANUFACTURER IN THIS PRODUCT IS LISTED AS A CARCINOGEN BY
    OSHA,IARC, NTP.
Effects of Overexposure:VAPORS IN HIGH CONCENTRATION ARE ANESTHETIC.
    OVEREXPOSURE MAY RESULT IN FATIGUE, WEAKNESS, CONFUSION EUPHORIA,
    DIZZINESS, HEADACHE, DILATED PUPILS, LACRIMATION, NERVOUSNESS,
    MUSCLE FATIGUE, INSOMNIA,  PARESTHESIA, DERMATITIS, AND
    PHOTOPHOBIA. CAN CAUSE TEARING, REDNESS OF EYES AND BLURRED VISION.
    IRRITATION OF SKIN.
Medical Cond Aggravated by Exposure:PERSONS WITH A HISTORY OF AILMENTS
    OR WITH A PRE-EXISTING DISEASE INVOLVING THE EYES, SKIN,
    RESPIRATORY TRACT OR NERVOUS SYSTEM MAY BE AT INCREASED RISK FROM
    EXPOSURE. DRYING/CRACKING OF SKIN.

=======================  First Aid Measures  =======================

First Aid:EYES: FLUSH WITH RUNNING WATER FOR 15 MINUTES WHILE HOLDING
    EYELID. GET MEDICAL ATTENTION IMMEDIATELY. SKIN: WASH WITH SOAP &
    WATER. REMOVE CONTAMINATED CLOTHING. GET MEDICAL ADVICE.
    INHALATION: REMOV E TO FRESH AIR. GIVE MOUTH-TO-MOUTH RESUSCITATION
    IF NOT BREATHING. GET MEDICAL ATTENTION. INGESTION: DO NOT INDUCE
    VOMITING. GIVE NOTHING BY MOUTH IF UNCONSCIOUS. GET MEDICAL
    ATTENTION IMMEDIATELY.

=====================  Fire Fighting Measures  =====================

Flash Point Method:PMCC
Flash Point:140F,60C
Autoignition Temp:Autoignition Temp Text:475F
Lower Limits:0.9
Upper Limits:7
Extinguishing Media:USE WATER FOG, CARBON DIOXIDE, FOAM, OR DRY
    CHEMICAL.
Fire Fighting Procedures:FIRE FIGHTERS SHOULD USE NIOSH APPROVED SCBA &
    FULL PROTECTIVE EQUIPMENT WHEN FIGHTING CHEMICAL FIRE. USE WATER
    SPRAY TO COOL NEARBY CONTAINERS EXPOSED TO FIRE.
Unusual Fire/Explosion Hazard:FIRE OR EXCESSIVE HEAT MAY CAUSE
    PRODUCTION OF HAZARDOUS DECOMPOSITION PRODUCTS. MATERIAL IS VERY
    VOLATILE AND GIVES OFF INVISIBLE VAPORS.

==================  Accidental Release Measures  ==================

Spill Release Procedures:REMOVE ALL SOURCES OF IGNITION. VENTILATE AND
    REMOVE WITH INERT ABSORBENT. USE NON-SPARKING TOOLS.

======================	Handling and Storage  ======================

Handling and Storage Precautions:CONTENTS ARE FLAMMABLE. KEEP AWAY FROM
    HEAT, SPARKS, AND OPEN FLAME. DURING USE AND UNTIL ALL VAPORS ARE
    GONE: KEEP AREA VENTILATED-DO NOT SMOKE.
Other Precautions:AVOID BREATHING OF VAPORS.

=============  Exposure Controls/Personal Protection  =============

Respiratory Protection:WEAR A NIOSH/MSHA APPROVED RESPIRATOR IF
    VENTILATION DOES NOT MAINTAIN INHALATION EXPOSURES BELOW PEL/TLV.
    WEAR SELF-CONTAINED BREATHING APPARATUS IF REQUIRED FOR HIGH LEVELS
    OF CONTAMINATES.
Ventilation:LOCAL EXHAUST PREFERABLE. GENERAL EXHAUST ACCEPTABLE IF THE
    EXPOSURE IS MAINTAINED BELOW APPLICABLE EXPOSURE LIMITS.
Protective Gloves:NEOPRENE OR NATURAL RUBBER GLOVES
Eye Protection:PAINT GOGGLES/SAFETY GLASSES AS REQUIRED
Other Protective Equipment:INDUSTRIAL-TYPE WORK CLOTHING, HAT AND APRON
    AS REQUIRED. AN EYE WASH AND DRENCH SHOWER FACILITY SHOULD BE
    AVAILABLE.
Work Hygienic Practices:USE WITH ADEQUATE VENTILATION. AVOID BREATHING
    VAPOR/SPRAY MIST. AVOID CONTACT WITH SKIN & EYES. WASH HANDS AFTER
    USE.
Supplemental Safety and Health
KEEP CONTAINER CLOSED WHEN NOT IN USE. TRANSFER ONLY TO APPROVED
    CONTAINERS WITH COMPLETE AND APPROPRIATE LABELING. DO NOT TAKE
    INTERNALLY.

==================  Physical/Chemical Properties  ==================

HCC:F4
Boiling Pt:B.P. Text:338F,170C
Melt/Freeze Pt:M.P/F.P Text:-51F,-46C
Vapor Pres:<5
Vapor Density:>5  AIR=1
Spec Gravity:0.788-0.845
pH:7
Viscosity:8.5 CST
Evaporation Rate & Reference:<0.05 (N-BUTYL ACETATE=1)
Solubility in Water:NEGLIGIBLE
Appearance and Odor:CLEAR WATER-WHITE LIQUID, FAINT PETROLEUM
    HYDROCARBON ODOR
Percent Volatiles by Volume:100

=================  Stability and Reactivity Data  =================

Stability Indicator/Materials to Avoid:YES
STRONG OXIDIZING AGENTS
Stability Condition to Avoid:HIGH TEMPERATURES, SPARKS, PILOT LIGHTS,
    STATIC ELECTRICITY, AND OPEN FLAMES
Hazardous Decomposition Products:BY FIRE: CARBON MONOXIDE, CARBON
    DIOXIDE, ALDEHYDES AND KETONES, OTHER INCOMPLETE COMBUSTION
    PRODUCTS.

====================  Disposal Considerations  ====================

Waste Disposal Methods:WASTE MATERIAL WILL LIKELY BE A HAZARDOUS WASTE
    (CODE D001) WHICH MUST BE DISPOSED OF ACCORDINGLY. DO NOT
    INCINERATE CLOSED CONTAINER. DISPOSE OF IN ACCORDANCE WITH FEDERAL,
    STATE AND LOCAL REGULATION S.

 Disclaimer (provided with this information by the compiling agencies):
 This information is formulated for use by elements of the Department
 of Defense.  The United States of America in no manner whatsoever,
 expressly or implied, warrants this information to be accurate and
 disclaims all liability for its use.  Any person utilizing this
 document should seek competent professional advice to verify and
 assume responsibility for the suitability of this information to their
 particular situation.